Contact person:
Shi Guoxi (General Manager) Tel: 13884663303
Wang Hongzhan (sales manager): 18865577323
Telephone\/Fax: 0535—6371732
Email:sdytruixing@163.com
Address: No. 10, Xiamen Street, Development Zone, Yantai City, Shandong Province
Automatic dosing machine operation steps
1. On the automatic dosing machine, click the "Settings" button in the upper left corner of the touch screen, select the drug name and relative process that need to be calibrated, and enter the dose that needs to be set.
2. Turn the "operation switch" on the control cabinet panel to the "automatic" position.
3. The measuring cup is required to detect the dosing points that need to be calibrated\/calibrated. During operation, only the dose flowing out once the solenoid valve is activated is detected.
4. The automatic dosing machine calculates the measured value and the set dose, for example:
The set dose is 2000ml. After testing, the dose flowing out once the solenoid valve is activated is: 200ml. Substitute into the formula "set dose\/valve activated dose once=valve activation frequency per minute" that is: 2000\/200=10 times, based on the solenoid valve per minute The activation frequency of the valve is less than 5 times. The above data exceeds the requirements, so it needs to be carried out.
Step 5 Adjustment. (If the frequency of opening of the solenoid valve is within the required range, the calibration data can be directly entered into the corresponding dosing point calibration interface) (Calibration interface: Click "Single Capacity Calibration" on the upper left side of the touch screen , select the name of the agent that needs to be calibrated, and enter the measured data after the corresponding dosing point).
5. On the automatic dosing machine, touch "Flux Setting" on the upper left corner of the display to enter the flux setting interface, and enter the corresponding time after the corresponding dosing point (time refers to: each time the solenoid valve is turned on time, the longer the time, the greater the flow, and vice versa).
Note: The automatic dosing machine has calculated that when the solenoid valve is turned on more than 5 times per minute, the flux time should be increased, and when the turn-on frequency is less than 1 time, the small flux time should be slowed down. The larger the flux time, the greater the flux time should not exceed 50 seconds. The minimum value shall not be less than 0.1 seconds.
Related News
- How to increase the service life of spiral scales
- The importance of using automatic ball adding machine
- Types and principles of automatic sampling machines
- Flow control and characteristics of diaphragm pump dosing machine
- How to choose the dosing location and method for peristaltic pump dosing machine
- Advantages and corrosion-resistant design features of solenoid valve dosing machine
- Common precautions when using electronic belt scales
- Characteristics, principles and maintenance of automatic dosing machines
- The composition and application of automatic dosing machine dosing equipment
- The reason why solenoid valve dosing machines are often used in the flotation process
- What are the characteristics of Ruixing solenoid valve dosing machine?
- Performance, function and maintenance of automatic dosing machine
- Application, maintenance and repair methods of flotation automatic dosing machine
- The role of automatic ball adding machine in the mineral processing process
- Flotation automatic dosing machine metering and control of flotation agent addition
- Development of flotation mineral processing and dosing system-solenoid valve dosing machine
- Instructions for use of flotation automatic dosing machine
- Flotation automatic dosing machine performs automatic and accurate dosing
- Application scope of automatic dosing machine
- Is it possible to configure the automatic sampler like this?